5kW 48V Garage Solar Wiring Diagram Printable (5S2P)

Computed 5kW 48V garage solar diagram: 5S2P array, wire gauges, OCPD, battery arrangement, routed parts and printable files.

5kW 48V Garage Solar Wiring Diagram Printable (5S2P) showing 5S2P panels, MPPT controller, 4S2P battery bank, wire gauges and OCPD ratings
Computed from the values printed in the schedules below; not a permit set.
View the scalable diagram inline5kW 48V Garage Solar Wiring Diagram Printable (5S2P)Computed 5S2P schematic for a 5 kW 48 V garage system, including wire and OCPD labels.FIG. OGA-LIBRARY-0875kW 48V Garage Solar Wiring Diagram Printable (5S2P)COMPUTED FROM OGA CALC-CORE · NOT A PERMIT SET8 AWG · 40 A OCPD · 1.04% drop3/0 AWG · 150 A OCPD · 0.30% drop1/0 AWG · 125 A OCPD · 0.10% drop10 × 500 W panels5S2P · 260 Voc / 23.6 IscCombiner2 stringsDC disconnect40 A DC ratedMPPT controller131 A min · 400 V max150 A OCPDController output8 × 120 Ah AGM4S2P · 11520 Wh bank125 A OCPDInverter feed4300 W inverter8600 W surge · 99.5 A DCShunt99.5 A monitored returnGround busEquipment groundingarray → controller8 AWG · 40 A OCPD · 1.04% drop40 ft one way · Coppercontroller → battery3/0 AWG · 150 A OCPD · 0.30% drop9 ft one way · Copperbattery → inverter1/0 AWG · 125 A OCPD · 0.10% drop2 ft one way · CopperPOSITIVENEGATIVEEQUIPMENT GROUNDFAILING SEGMENTNEC 2023 Table 310.16 (60 C column) - conductor ampacityNEC Chapter 9, Table 8 - conductor DC resistanceNEC 240.6(A) - standard overcurrent-device ratingsNEC 210.19 / 215.2 - 125% continuous-load conductor sizingNEC 690.7 - maximum PV source-circuit voltageNEC 690.8 - PV source-circuit current sizingVerify equipment terminals, listings, ambient/bundling derates and local code before installation.

What this computed plan shows

Numbers, not decorative lines, define the 5kW 48V Garage Solar Wiring Diagram Printable (5S2P). The 5S2P field connects 10 panels for 5 kW of nameplate power, 220 operating volts and 23.6 short-circuit amps. That combination gives a garage builder a concrete starting case that can be changed in the linked customizer.

A MPPT device is shown because the array and bank operate at different useful voltage points. The engine calculates 130.2 A of required controller output and tests 325 V against a 400 V input rating. These limits should be matched to a manufacturer datasheet, including its temperature assumptions.

On the first two protected runs, the schedule pairs 40 A with 8 AWG copper and 150 A with 3/0 AWG copper. The corresponding one-way distances are 40 ft and 9 ft, producing 1.04% and 0.3% drop. These values assume the stated conductor material and do not include unverified ambient or bundling derates.

The battery table translates 8 individual 120 Ah units into a 4S2P bank. In this 48 V design, the result is 240 Ah and 11,520 Wh of nominal storage. Usable energy will be lower and depends on chemistry limits, temperature, battery management and the connected load profile.

At the final DC segment, the current rises to 99.5 A for a 4,300 W inverter. The page assigns 1/0 AWG copper to the 2 ft route, with 125 A OCPD and 0.1% calculated drop. Termination ratings and the inverter maker’s fuse instructions remain controlling.

The generated SVG, PNG and tables intentionally repeat the same computed labels so discrepancies are visible during review. If a purchased controller, battery or inverter differs from the values above, regenerate the design from the linked machine before wiring. This garage example is not a permit set and does not replace equipment instructions or a qualified local professional.

For later comparison, keep the 5 kW array, 4S2P bank and the 40/9/2 ft one-way routes together when requesting equipment quotes or an inspection review.

Wire, protection and battery schedules

Wire schedule

SegmentDesign currentOne-way runComputed conductorVoltage dropSizing basis
array → controller36.8 A40 ft8 AWG copper1.04%156% of array Isc (NEC 690.8)
controller → battery104.2 A9 ft3/0 AWG copper0.3%controller output at 125% continuous-load ampacity
battery → inverter99.5 A2 ft1/0 AWG copper0.1%inverter continuous DC input at 90% efficiency and 125% ampacity

Overcurrent protection

Protected segmentRequired ampacityOCPDConductor ampacityVerdict
array → controller36.8 A40 A40 Awithin
controller → battery130.2 A150 A165 Awithin
battery → inverter124.4 A125 A125 Awithin

Battery arrangement

ArrangementChemistryUnitsUnit capacityBank capacityNominal energyNominal voltage
4S2PAGM8120 Ah240 Ah11,520 Wh48 V

Static routed parts list

Parts are computed from this passing configuration. A route appears only when the verified catalogue record proves every displayed numeric rating; all uncertain matches stay local for verification. Routed links may earn Off Grid Authority a commission at no extra cost to you.

10 × 500 W solar panelVoc 52 V, Vmp 44 V, Isc 11.8 AVerify locally — no proven catalogue match
1 × MPPT charge controllerat least 131 A output and 325 V PV inputVerify locally — no proven catalogue match
8 × 120 Ah AGM battery4S2P bank, 11520 Wh nominalVerify locally — no proven catalogue match
1 × 4300 W inverter8600 W surge, 48 V DC inputVerify locally — no proven catalogue match
90 ft × 8 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 8 AWGVerify locally — no proven catalogue match
1 × 40 A breaker / fuseDC-rated, 220 V system — must not exceed the wire's 40 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
25 ft × 3/0 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 3/0 AWGVerify locally — no proven catalogue match
1 × 150 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 165 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
10 ft × 1/0 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 1/0 AWGVerify locally — no proven catalogue match
1 × 125 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 125 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match

Pre-install review steps

  1. Confirm the array and controller window: Verify that the 5S2P string plan produces 260 V open circuit and that the equipment is rated above the 325 V cold-design value.
  2. Lay out the protected DC runs: Measure the one-way paths before ordering cable, then compare them with the computed 40 ft, 9 ft and 2 ft runs shown here.
  3. Build complete battery strings: Arrange all 8 battery units as 4S2P; do not leave a partial series string in a 48 V bank.
  4. Commission against equipment instructions: Check polarity, terminal torque, DC interrupt ratings, conductor temperature ratings, ambient correction and local inspection requirements before energizing the 4,300 W inverter.

Customize or compare

Customize this diagram →

Open the parent build guide for the surrounding design context, safety notes and installation discussion.