4800W 48V Off-Grid Solar Wiring Diagram Printable (4S3P)

Computed 4800W 48V off-grid solar system solar diagram: 4S3P array, wire gauges, OCPD, battery arrangement, routed parts and printable files.

4800W 48V Off-Grid Solar Wiring Diagram Printable (4S3P) showing 4S3P panels, MPPT controller, 4S2P battery bank, wire gauges and OCPD ratings
Computed from the values printed in the schedules below; not a permit set.
View the scalable diagram inline4800W 48V Off-Grid Solar Wiring Diagram Printable (4S3P)Computed 4S3P schematic for a 4,800 W 48 V off-grid solar system system, including wire and OCPD labels.FIG. OGA-LIBRARY-0144800W 48V Off-Grid Solar Wiring Diagram Printable (4S3P)COMPUTED FROM OGA CALC-CORE · NOT A PERMIT SET6 AWG · 50 A OCPD · 0.34% drop1/0 AWG · 125 A OCPD · 0.46% drop4/0 AWG · 175 A OCPD · 0.16% drop12 × 400 W panels4S3P · 198 Voc / 30.6 IscCombiner3 stringsDC disconnect50 A DC ratedMPPT controller125 A min · 300 V max125 A OCPDController output8 × 120 Ah AGM4S2P · 11520 Wh bank175 A OCPDInverter feed5600 W inverter11200 W surge · 129.6 A DCShunt129.6 A monitored returnGround busEquipment groundingarray → controller6 AWG · 50 A OCPD · 0.34% drop12 ft one way · Coppercontroller → battery1/0 AWG · 125 A OCPD · 0.46% drop9 ft one way · Copperbattery → inverter4/0 AWG · 175 A OCPD · 0.16% drop5 ft one way · CopperPOSITIVENEGATIVEEQUIPMENT GROUNDFAILING SEGMENTNEC 2023 Table 310.16 (60 C column) - conductor ampacityNEC Chapter 9, Table 8 - conductor DC resistanceNEC 240.6(A) - standard overcurrent-device ratingsNEC 210.19 / 215.2 - 125% continuous-load conductor sizingNEC 690.7 - maximum PV source-circuit voltageNEC 690.8 - PV source-circuit current sizingVerify equipment terminals, listings, ambient/bundling derates and local code before installation.

What this computed plan shows

Searchers asking for “12 volt off grid solar system wiring diagram pdf” usually need more than a block diagram. This 4800W 48V Off-Grid Solar Wiring Diagram Printable (4S3P) therefore fixes the panel count, string arrangement, controller window, storage layout and inverter feed as one computed off-grid solar system example. With 12 panels wired 4S3P, the array totals 4,800 W and reaches 198 Voc at nameplate conditions.

At the charge controller, the drawing records a 125 A minimum and a 247.5 V design Voc. Those are different questions: one protects adequate charging output, while the other keeps the 4S3P string below the equipment’s 300 V input limit. Both checks return within for this exact 4800W 48V Off-Grid Solar Wiring Diagram Printable (4S3P) state.

The array-to-controller route is 12 ft one way and carries 47.7 design amps. It resolves to 6 AWG copper, a 50 A OCPD and 0.34% calculated drop. Downstream, the 9 ft controller lead uses 1/0 AWG copper behind 125 A protection, holding its computed drop to 0.46%.

Storage is drawn as 4S2P: 8 AGM units, each 120 Ah. That produces 240 Ah at 48 V and 11,520 Wh nominal. The complete-series-string rule is why the count and arrangement appear together rather than as an interchangeable battery total.

A 5,600 W continuous inverter draws about 129.6 A from this 48 V bank under the stated efficiency assumption. The 5 ft feed therefore becomes 4/0 AWG copper, protected at 175 A and calculated at 0.16% drop. Keeping this high-current run short is usually more effective than buying around a poor layout.

All three schedule rows pass the shared ampacity and voltage-drop checks for the inputs printed here. That does not account for every field condition, including conduit fill, grouped conductors, engine-room heat, corrosion exposure or manufacturer-specific terminal limits. Treat the 4800W 48V Off-Grid Solar Wiring Diagram Printable (4S3P) as a traceable calculation snapshot and have work reviewed whenever the installation falls outside its displayed assumptions.

For later comparison, keep the 4,800 W array, 4S2P bank and the 12/9/5 ft one-way routes together when requesting equipment quotes or an inspection review.

Wire, protection and battery schedules

Wire schedule

SegmentDesign currentOne-way runComputed conductorVoltage dropSizing basis
array → controller47.7 A12 ft6 AWG copper0.34%156% of array Isc (NEC 690.8)
controller → battery100 A9 ft1/0 AWG copper0.46%controller output at 125% continuous-load ampacity
battery → inverter129.6 A5 ft4/0 AWG copper0.16%inverter continuous DC input at 90% efficiency and 125% ampacity

Overcurrent protection

Protected segmentRequired ampacityOCPDConductor ampacityVerdict
array → controller47.7 A50 A55 Awithin
controller → battery125 A125 A125 Awithin
battery → inverter162 A175 A195 Awithin

Battery arrangement

ArrangementChemistryUnitsUnit capacityBank capacityNominal energyNominal voltage
4S2PAGM8120 Ah240 Ah11,520 Wh48 V

Static routed parts list

Parts are computed from this passing configuration. A route appears only when the verified catalogue record proves every displayed numeric rating; all uncertain matches stay local for verification. Routed links may earn Off Grid Authority a commission at no extra cost to you.

12 × 400 W solar panelVoc 49.5 V, Vmp 41 V, Isc 10.2 AVerify locally — no proven catalogue match
1 × MPPT charge controllerat least 125 A output and 248 V PV inputVerify locally — no proven catalogue match
8 × 120 Ah AGM battery4S2P bank, 11520 Wh nominalVerify locally — no proven catalogue match
1 × 5600 W inverter11200 W surge, 48 V DC inputVerify locally — no proven catalogue match
30 ft × 6 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 6 AWGVerify locally — no proven catalogue match
1 × 50 A breaker / fuseDC-rated, 164 V system — must not exceed the wire's 55 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
25 ft × 1/0 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 1/0 AWGVerify locally — no proven catalogue match
1 × 125 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 125 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
20 ft × 4/0 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 4/0 AWGVerify locally — no proven catalogue match
1 × 175 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 195 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match

Pre-install review steps

  1. Confirm the array and controller window: Verify that the 4S3P string plan produces 198 V open circuit and that the equipment is rated above the 247.5 V cold-design value.
  2. Lay out the protected DC runs: Measure the one-way paths before ordering cable, then compare them with the computed 12 ft, 9 ft and 5 ft runs shown here.
  3. Build complete battery strings: Arrange all 8 battery units as 4S2P; do not leave a partial series string in a 48 V bank.
  4. Commission against equipment instructions: Check polarity, terminal torque, DC interrupt ratings, conductor temperature ratings, ambient correction and local inspection requirements before energizing the 5,600 W inverter.

Customize or compare

Customize this diagram →

Open the parent build guide for the surrounding design context, safety notes and installation discussion.