5kW 48V Off-Grid Solar Wiring Diagram Complete (5S2P)

Computed 5kW 48V off-grid solar system solar diagram: 5S2P array, wire gauges, OCPD, battery arrangement, routed parts and printable files.

5kW 48V Off-Grid Solar Wiring Diagram Complete (5S2P) showing 5S2P panels, MPPT controller, 4S3P battery bank, wire gauges and OCPD ratings
Computed from the values printed in the schedules below; not a permit set.
View the scalable diagram inline5kW 48V Off-Grid Solar Wiring Diagram Complete (5S2P)Computed 5S2P schematic for a 5 kW 48 V off-grid solar system system, including wire and OCPD labels.FIG. OGA-LIBRARY-0125kW 48V Off-Grid Solar Wiring Diagram Complete (5S2P)COMPUTED FROM OGA CALC-CORE · NOT A PERMIT SET8 AWG · 40 A OCPD · 1.17% drop3/0 AWG · 150 A OCPD · 0.17% drop3/0 AWG · 150 A OCPD · 0.11% drop10 × 500 W panels5S2P · 260 Voc / 23.6 IscCombiner2 stringsDC disconnect40 A DC ratedMPPT controller131 A min · 400 V max150 A OCPDController output12 × 200 Ah Flooded4S3P · 28800 Wh bank150 A OCPDInverter feed4800 W inverter9600 W surge · 111.1 A DCShunt111.1 A monitored returnGround busEquipment groundingarray → controller8 AWG · 40 A OCPD · 1.17% drop45 ft one way · Coppercontroller → battery3/0 AWG · 150 A OCPD · 0.17% drop5 ft one way · Copperbattery → inverter3/0 AWG · 150 A OCPD · 0.11% drop3 ft one way · CopperPOSITIVENEGATIVEEQUIPMENT GROUNDFAILING SEGMENTNEC 2023 Table 310.16 (60 C column) - conductor ampacityNEC Chapter 9, Table 8 - conductor DC resistanceNEC 240.6(A) - standard overcurrent-device ratingsNEC 210.19 / 215.2 - 125% continuous-load conductor sizingNEC 690.7 - maximum PV source-circuit voltageNEC 690.8 - PV source-circuit current sizingVerify equipment terminals, listings, ambient/bundling derates and local code before installation.

What this computed plan shows

For the 5kW 48V Off-Grid Solar Wiring Diagram Complete (5S2P), a 5S2P array gives 5 kW of rated panel capacity for the off-grid solar system use case. Nameplate multiplication produces 260 Voc, 220 Vmp and 23.6 Isc at the combined array. Those values are carried forward into controller and conductor checks instead of being rounded into a one-size-fits-all diagram.

The MPPT controller needs at least 131 A of output capacity. Its PV input must also remain above the engine’s 325 V cold-design check, while the configured ceiling is 400 V. That margin matters because the diagram’s 260 V nameplate value is not the final controller comparison value.

On the first two protected runs, the schedule pairs 40 A with 8 AWG copper and 150 A with 3/0 AWG copper. The corresponding one-way distances are 45 ft and 5 ft, producing 1.17% and 0.17% drop. These values assume the stated conductor material and do not include unverified ambient or bundling derates.

A 4S3P layout keeps every battery in a complete 48 V string. Using 12 Flooded units at 200 Ah each yields 600 bank amp-hours and 28,800 nominal watt-hours. Parallel paths still need equal cable geometry, suitable disconnecting means and manufacturer-approved protection.

The battery-to-inverter path is only 3 ft, but it carries 111.1 A continuously in the calculation. That combination selects 3/0 AWG copper and 150 A protection while retaining 0.11% drop. The 9,600 W surge figure should be compared with motor or compressor starting loads separately from continuous power.

Use the parts links as a routed specification checklist, not permission to substitute unlike ratings. Before buying, confirm controller voltage, breaker interrupt rating, conductor insulation, terminal temperature class, battery series approval and inverter DC range. The customizer carries this exact 5kW 48V Off-Grid Solar Wiring Diagram Complete (5S2P) state in its URL hash so run lengths or nameplate values can be changed without editing the static drawing.

For later comparison, keep the 5 kW array, 4S3P bank and the 45/5/3 ft one-way routes together when requesting equipment quotes or an inspection review.

Wire, protection and battery schedules

Wire schedule

SegmentDesign currentOne-way runComputed conductorVoltage dropSizing basis
array → controller36.8 A45 ft8 AWG copper1.17%156% of array Isc (NEC 690.8)
controller → battery104.2 A5 ft3/0 AWG copper0.17%controller output at 125% continuous-load ampacity
battery → inverter111.1 A3 ft3/0 AWG copper0.11%inverter continuous DC input at 90% efficiency and 125% ampacity

Overcurrent protection

Protected segmentRequired ampacityOCPDConductor ampacityVerdict
array → controller36.8 A40 A40 Awithin
controller → battery130.2 A150 A165 Awithin
battery → inverter138.9 A150 A165 Awithin

Battery arrangement

ArrangementChemistryUnitsUnit capacityBank capacityNominal energyNominal voltage
4S3PFlooded12200 Ah600 Ah28,800 Wh48 V

Static routed parts list

Parts are computed from this passing configuration. A route appears only when the verified catalogue record proves every displayed numeric rating; all uncertain matches stay local for verification. Routed links may earn Off Grid Authority a commission at no extra cost to you.

10 × 500 W solar panelVoc 52 V, Vmp 44 V, Isc 11.8 AVerify locally — no proven catalogue match
1 × MPPT charge controllerat least 131 A output and 325 V PV inputVerify locally — no proven catalogue match
12 × 200 Ah Flooded battery4S3P bank, 28800 Wh nominalVerify locally — no proven catalogue match
1 × 4800 W inverter9600 W surge, 48 V DC inputVerify locally — no proven catalogue match
100 ft × 8 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 8 AWGVerify locally — no proven catalogue match
1 × 40 A breaker / fuseDC-rated, 220 V system — must not exceed the wire's 40 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
20 ft × 3/0 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 3/0 AWGVerify locally — no proven catalogue match
1 × 150 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 165 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
15 ft × 3/0 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 3/0 AWGVerify locally — no proven catalogue match
1 × 150 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 165 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match

Pre-install review steps

  1. Confirm the array and controller window: Verify that the 5S2P string plan produces 260 V open circuit and that the equipment is rated above the 325 V cold-design value.
  2. Lay out the protected DC runs: Measure the one-way paths before ordering cable, then compare them with the computed 45 ft, 5 ft and 3 ft runs shown here.
  3. Build complete battery strings: Arrange all 12 battery units as 4S3P; do not leave a partial series string in a 48 V bank.
  4. Commission against equipment instructions: Check polarity, terminal torque, DC interrupt ratings, conductor temperature ratings, ambient correction and local inspection requirements before energizing the 4,800 W inverter.

Customize or compare

Customize this diagram →

Open the parent build guide for the surrounding design context, safety notes and installation discussion.