6kW 48V Workshop Solar Wiring Diagram Printable (6S2P)

Computed 6kW 48V workshop solar diagram: 6S2P array, wire gauges, OCPD, battery arrangement, routed parts and printable files.

6kW 48V Workshop Solar Wiring Diagram Printable (6S2P) showing 6S2P panels, MPPT controller, 4S2P battery bank, wire gauges and OCPD ratings
Computed from the values printed in the schedules below; not a permit set.
View the scalable diagram inline6kW 48V Workshop Solar Wiring Diagram Printable (6S2P)Computed 6S2P schematic for a 6 kW 48 V workshop system, including wire and OCPD labels.FIG. OGA-LIBRARY-0946kW 48V Workshop Solar Wiring Diagram Printable (6S2P)COMPUTED FROM OGA CALC-CORE · NOT A PERMIT SET8 AWG · 40 A OCPD · 0.95% drop4/0 AWG · 175 A OCPD · 0.25% drop1/0 AWG · 125 A OCPD · 0.15% drop12 × 500 W panels6S2P · 312 Voc / 23.6 IscCombiner2 stringsDC disconnect40 A DC ratedMPPT controller157 A min · 450 V max175 A OCPDController output8 × 120 Ah AGM4S2P · 11520 Wh bank125 A OCPDInverter feed4200 W inverter8400 W surge · 97.2 A DCShunt97.2 A monitored returnGround busEquipment groundingarray → controller8 AWG · 40 A OCPD · 0.95% drop44 ft one way · Coppercontroller → battery4/0 AWG · 175 A OCPD · 0.25% drop8 ft one way · Copperbattery → inverter1/0 AWG · 125 A OCPD · 0.15% drop3 ft one way · CopperPOSITIVENEGATIVEEQUIPMENT GROUNDFAILING SEGMENTNEC 2023 Table 310.16 (60 C column) - conductor ampacityNEC Chapter 9, Table 8 - conductor DC resistanceNEC 240.6(A) - standard overcurrent-device ratingsNEC 210.19 / 215.2 - 125% continuous-load conductor sizingNEC 690.7 - maximum PV source-circuit voltageNEC 690.8 - PV source-circuit current sizingVerify equipment terminals, listings, ambient/bundling derates and local code before installation.

What this computed plan shows

Built around a 6 kW array, the 6kW 48V Workshop Solar Wiring Diagram Printable (6S2P) is a computed answer to the demand phrasing “workshop solar power system.” The diagram shows 12 modules as 6S2P, not an unspecified bank of panels, and it carries 312 Voc plus 22.7 operating amps into the controller review. Every table on this page describes that same state.

At the charge controller, the drawing records a 157 A minimum and a 390 V design Voc. Those are different questions: one protects adequate charging output, while the other keeps the 6S2P string below the equipment’s 450 V input limit. Both checks return within for this exact 6kW 48V Workshop Solar Wiring Diagram Printable (6S2P) state.

The array-to-controller route is 44 ft one way and carries 36.8 design amps. It resolves to 8 AWG copper, a 40 A OCPD and 0.95% calculated drop. Downstream, the 8 ft controller lead uses 4/0 AWG copper behind 175 A protection, holding its computed drop to 0.25%.

Storage is drawn as 4S2P: 8 AGM units, each 120 Ah. That produces 240 Ah at 48 V and 11,520 Wh nominal. The complete-series-string rule is why the count and arrangement appear together rather than as an interchangeable battery total.

A 4,200 W continuous inverter draws about 97.2 A from this 48 V bank under the stated efficiency assumption. The 3 ft feed therefore becomes 1/0 AWG copper, protected at 125 A and calculated at 0.15% drop. Keeping this high-current run short is usually more effective than buying around a poor layout.

All three schedule rows pass the shared ampacity and voltage-drop checks for the inputs printed here. That does not account for every field condition, including conduit fill, grouped conductors, engine-room heat, corrosion exposure or manufacturer-specific terminal limits. Treat the 6kW 48V Workshop Solar Wiring Diagram Printable (6S2P) as a traceable calculation snapshot and have work reviewed whenever the installation falls outside its displayed assumptions.

For later comparison, keep the 6 kW array, 4S2P bank and the 44/8/3 ft one-way routes together when requesting equipment quotes or an inspection review.

Wire, protection and battery schedules

Wire schedule

SegmentDesign currentOne-way runComputed conductorVoltage dropSizing basis
array → controller36.8 A44 ft8 AWG copper0.95%156% of array Isc (NEC 690.8)
controller → battery125 A8 ft4/0 AWG copper0.25%controller output at 125% continuous-load ampacity
battery → inverter97.2 A3 ft1/0 AWG copper0.15%inverter continuous DC input at 90% efficiency and 125% ampacity

Overcurrent protection

Protected segmentRequired ampacityOCPDConductor ampacityVerdict
array → controller36.8 A40 A40 Awithin
controller → battery156.3 A175 A195 Awithin
battery → inverter121.5 A125 A125 Awithin

Battery arrangement

ArrangementChemistryUnitsUnit capacityBank capacityNominal energyNominal voltage
4S2PAGM8120 Ah240 Ah11,520 Wh48 V

Static routed parts list

Parts are computed from this passing configuration. A route appears only when the verified catalogue record proves every displayed numeric rating; all uncertain matches stay local for verification. Routed links may earn Off Grid Authority a commission at no extra cost to you.

12 × 500 W solar panelVoc 52 V, Vmp 44 V, Isc 11.8 AVerify locally — no proven catalogue match
1 × MPPT charge controllerat least 157 A output and 390 V PV inputVerify locally — no proven catalogue match
8 × 120 Ah AGM battery4S2P bank, 11520 Wh nominalVerify locally — no proven catalogue match
1 × 4200 W inverter8400 W surge, 48 V DC inputVerify locally — no proven catalogue match
95 ft × 8 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 8 AWGVerify locally — no proven catalogue match
1 × 40 A breaker / fuseDC-rated, 264 V system — must not exceed the wire's 40 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
25 ft × 4/0 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 4/0 AWGVerify locally — no proven catalogue match
1 × 175 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 195 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
15 ft × 1/0 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 1/0 AWGVerify locally — no proven catalogue match
1 × 125 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 125 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match

Pre-install review steps

  1. Confirm the array and controller window: Verify that the 6S2P string plan produces 312 V open circuit and that the equipment is rated above the 390 V cold-design value.
  2. Lay out the protected DC runs: Measure the one-way paths before ordering cable, then compare them with the computed 44 ft, 8 ft and 3 ft runs shown here.
  3. Build complete battery strings: Arrange all 8 battery units as 4S2P; do not leave a partial series string in a 48 V bank.
  4. Commission against equipment instructions: Check polarity, terminal torque, DC interrupt ratings, conductor temperature ratings, ambient correction and local inspection requirements before energizing the 4,200 W inverter.

Customize or compare

Customize this diagram →

Open the parent build guide for the surrounding design context, safety notes and installation discussion.