1200W 24V Well-Pump Solar Wiring Diagram Complete (2S2P)

Computed 1200W 24V well pump solar diagram: 2S2P array, wire gauges, OCPD, battery arrangement, routed parts and printable files.

1200W 24V Well-Pump Solar Wiring Diagram Complete (2S2P) showing 2S2P panels, MPPT controller, 2S1P battery bank, wire gauges and OCPD ratings
Computed from the values printed in the schedules below; not a permit set.
View the scalable diagram inline1200W 24V Well-Pump Solar Wiring Diagram Complete (2S2P)Computed 2S2P schematic for a 1,200 W 24 V well pump system, including wire and OCPD labels.FIG. OGA-LIBRARY-1151200W 24V Well-Pump Solar Wiring Diagram Complete (2S2P)COMPUTED FROM OGA CALC-CORE · NOT A PERMIT SET8 AWG · 35 A OCPD · 1.82% drop4 AWG · 70 A OCPD · 1.16% drop3/0 AWG · 150 A OCPD · 0.20% drop4 × 300 W panels2S2P · 75 Voc / 20.2 IscCombiner2 stringsDC disconnect35 A DC ratedMPPT controller63 A min · 150 V max70 A OCPDController output2 × 100 Ah AGM2S1P · 2400 Wh bank150 A OCPDInverter feed2300 W inverter4600 W surge · 106.5 A DCShunt106.5 A monitored returnGround busEquipment groundingarray → controller8 AWG · 35 A OCPD · 1.82% drop23 ft one way · Coppercontroller → battery4 AWG · 70 A OCPD · 1.16% drop9 ft one way · Copperbattery → inverter3/0 AWG · 150 A OCPD · 0.20% drop3 ft one way · CopperPOSITIVENEGATIVEEQUIPMENT GROUNDFAILING SEGMENTNEC 2023 Table 310.16 (60 C column) - conductor ampacityNEC Chapter 9, Table 8 - conductor DC resistanceNEC 240.6(A) - standard overcurrent-device ratingsNEC 210.19 / 215.2 - 125% continuous-load conductor sizingNEC 690.7 - maximum PV source-circuit voltageNEC 690.8 - PV source-circuit current sizingVerify equipment terminals, listings, ambient/bundling derates and local code before installation.

What this computed plan shows

The 1200W 24V Well-Pump Solar Wiring Diagram Complete (2S2P) turns a searched-for well pump idea into one internally consistent DC schematic. Its 1,200 W array uses 4 modules in 2S2P, so the drawing labels the array at 62 Vmp and 20.2 Isc rather than relying on a generic icon. The result is a planning reference for comparing real equipment ratings before installation.

A MPPT device is shown because the array and bank operate at different useful voltage points. The engine calculates 62.5 A of required controller output and tests 93.8 V against a 150 V input rating. These limits should be matched to a manufacturer datasheet, including its temperature assumptions.

Starting at the roof or rack, 8 AWG copper covers the 23 ft PV run with 1.82% drop and a 35 A protective device. The controller-to-bank segment is shorter at 9 ft, yet its 50 A design current calls for 4 AWG copper and 70 A OCPD. Distance and current are both visible because either can determine conductor size.

The battery table translates 2 individual 100 Ah units into a 2S1P bank. In this 24 V design, the result is 100 Ah and 2,400 Wh of nominal storage. Usable energy will be lower and depends on chemistry limits, temperature, battery management and the connected load profile.

At the final DC segment, the current rises to 106.5 A for a 2,300 W inverter. The page assigns 3/0 AWG copper to the 3 ft route, with 150 A OCPD and 0.2% calculated drop. Termination ratings and the inverter maker’s fuse instructions remain controlling.

The generated SVG, PNG and tables intentionally repeat the same computed labels so discrepancies are visible during review. If a purchased controller, battery or inverter differs from the values above, regenerate the design from the linked machine before wiring. This well pump example is not a permit set and does not replace equipment instructions or a qualified local professional.

For later comparison, keep the 1,200 W array, 2S1P bank and the 23/9/3 ft one-way routes together when requesting equipment quotes or an inspection review.

Wire, protection and battery schedules

Wire schedule

SegmentDesign currentOne-way runComputed conductorVoltage dropSizing basis
array → controller31.5 A23 ft8 AWG copper1.82%156% of array Isc (NEC 690.8)
controller → battery50 A9 ft4 AWG copper1.16%controller output at 125% continuous-load ampacity
battery → inverter106.5 A3 ft3/0 AWG copper0.2%inverter continuous DC input at 90% efficiency and 125% ampacity

Overcurrent protection

Protected segmentRequired ampacityOCPDConductor ampacityVerdict
array → controller31.5 A35 A40 Awithin
controller → battery62.5 A70 A70 Awithin
battery → inverter133.1 A150 A165 Awithin

Battery arrangement

ArrangementChemistryUnitsUnit capacityBank capacityNominal energyNominal voltage
2S1PAGM2100 Ah100 Ah2,400 Wh24 V

Static routed parts list

Parts are computed from this passing configuration. A route appears only when the verified catalogue record proves every displayed numeric rating; all uncertain matches stay local for verification. Routed links may earn Off Grid Authority a commission at no extra cost to you.

4 × 300 W solar panelVoc 37.5 V, Vmp 31 V, Isc 10.1 AVerify locally — no proven catalogue match
1 × MPPT charge controllerat least 63 A output and 94 V PV inputVerify locally — no proven catalogue match
2 × 100 Ah AGM battery2S1P bank, 2400 Wh nominalVerify locally — no proven catalogue match
1 × 2300 W inverter4600 W surge, 24 V DC inputVerify locally — no proven catalogue match
55 ft × 8 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 8 AWGVerify locally — no proven catalogue match
1 × 35 A breaker / fuseDC-rated, 62 V system — must not exceed the wire's 40 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
25 ft × 4 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 4 AWGVerify locally — no proven catalogue match
1 × 70 A breaker / fuseDC-rated, 24 V system — must not exceed the wire's 70 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
15 ft × 3/0 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 3/0 AWGVerify locally — no proven catalogue match
1 × 150 A breaker / fuseDC-rated, 24 V system — must not exceed the wire's 165 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match

Pre-install review steps

  1. Confirm the array and controller window: Verify that the 2S2P string plan produces 75 V open circuit and that the equipment is rated above the 93.8 V cold-design value.
  2. Lay out the protected DC runs: Measure the one-way paths before ordering cable, then compare them with the computed 23 ft, 9 ft and 3 ft runs shown here.
  3. Build complete battery strings: Arrange all 2 battery units as 2S1P; do not leave a partial series string in a 24 V bank.
  4. Commission against equipment instructions: Check polarity, terminal torque, DC interrupt ratings, conductor temperature ratings, ambient correction and local inspection requirements before energizing the 2,300 W inverter.

Customize or compare

Customize this diagram →

Open the parent build guide for the surrounding design context, safety notes and installation discussion.