Engine-checked · within

2100W 48V Well-Pump Solar Wiring Diagram with Battery (3S2P)

Computed 2100W 48V well pump solar diagram: 3S2P array, wire gauges, OCPD, battery arrangement, routed parts and printable files.

2100W 48V Well-Pump Solar Wiring Diagram with Battery (3S2P) showing 3S2P panels, MPPT controller, 4S1P battery bank, wire gauges and OCPD ratings
Computed from the values printed in the schedules below; not a permit set.
View the scalable diagram inline2100W 48V Well-Pump Solar Wiring Diagram with Battery (3S2P)Computed 3S2P schematic for a 2,100 W 48 V well pump system, including wire and OCPD labels.FIG. OGA-LIBRARY-1182100W 48V Well-Pump Solar Wiring Diagram with Battery (3S2P)COMPUTED FROM OGA CALC-CORE · NOT A PERMIT SET8 AWG · 35 A OCPD · 1.40% drop4 AWG · 60 A OCPD · 0.45% drop1 AWG · 100 A OCPD · 0.30% drop6 × 350 W panels3S2P · 135 Voc / 20 IscCombiner2 stringsDC disconnect35 A DC ratedMPPT controller55 A min · 250 V max60 A OCPDController output4 × 100 Ah LiFePO₄4S1P · 5120 Wh bank100 A OCPDInverter feed3350 W inverter6700 W surge · 77.5 A DCShunt77.5 A monitored returnGround busEquipment groundingarray → controller8 AWG · 35 A OCPD · 1.40% drop32 ft one way · Coppercontroller → battery4 AWG · 60 A OCPD · 0.45% drop8 ft one way · Copperbattery → inverter1 AWG · 100 A OCPD · 0.30% drop6 ft one way · CopperPOSITIVENEGATIVEEQUIPMENT GROUNDFAILING SEGMENTNEC 2023 Table 310.16 (60 C column) - conductor ampacityNEC Chapter 9, Table 8 - conductor DC resistanceNEC 240.6(A) - standard overcurrent-device ratingsNEC 210.19 / 215.2 - 125% continuous-load conductor sizingNEC 690.7 - maximum PV source-circuit voltageNEC 690.8 - PV source-circuit current sizingVerify equipment terminals, listings, ambient/bundling derates and local code before installation.

What this computed plan shows

Built around a 2,100 W array, the 2100W 48V Well-Pump Solar Wiring Diagram with Battery (3S2P) is a computed answer to the demand phrasing “solar powered well pump in oasis.” The diagram shows 6 modules as 3S2P, not an unspecified bank of panels, and it carries 135 Voc plus 18.9 operating amps into the controller review. Every table on this page describes that same state.

At the charge controller, the drawing records a 55 A minimum and a 168.8 V design Voc. Those are different questions: one protects adequate charging output, while the other keeps the 3S2P string below the equipment’s 250 V input limit. Both checks return within for this exact 2100W 48V Well-Pump Solar Wiring Diagram with Battery (3S2P) state.

PV current is evaluated at 31.2 A for the 32 ft array run, which selects 8 AWG copper plus a 35 A OCPD. Charging current is 43.8 A across 8 ft, moving the recommendation to 4 AWG copper with 60 A protection. Each percentage in the table is a round-trip voltage-drop calculation.

Storage is drawn as 4S1P: 4 LiFePO₄ units, each 100 Ah. That produces 100 Ah at 48 V and 5,120 Wh nominal. The complete-series-string rule is why the count and arrangement appear together rather than as an interchangeable battery total.

A 3,350 W continuous inverter draws about 77.5 A from this 48 V bank under the stated efficiency assumption. The 6 ft feed therefore becomes 1 AWG copper, protected at 100 A and calculated at 0.3% drop. Keeping this high-current run short is usually more effective than buying around a poor layout.

All three schedule rows pass the shared ampacity and voltage-drop checks for the inputs printed here. That does not account for every field condition, including conduit fill, grouped conductors, engine-room heat, corrosion exposure or manufacturer-specific terminal limits. Treat the 2100W 48V Well-Pump Solar Wiring Diagram with Battery (3S2P) as a traceable calculation snapshot and have work reviewed whenever the installation falls outside its displayed assumptions.

For later comparison, keep the 2,100 W array, 4S1P bank and the 32/8/6 ft one-way routes together when requesting equipment quotes or an inspection review.

Wire, protection and battery schedules

Wire schedule

SegmentDesign currentOne-way runComputed conductorVoltage dropSizing basis
array → controller31.2 A32 ft8 AWG copper1.4%156% of array Isc (NEC 690.8)
controller → battery43.8 A8 ft4 AWG copper0.45%controller output at 125% continuous-load ampacity
battery → inverter77.5 A6 ft1 AWG copper0.3%inverter continuous DC input at 90% efficiency and 125% ampacity

Overcurrent protection

Protected segmentRequired ampacityOCPDConductor ampacityVerdict
array → controller31.2 A35 A40 Awithin
controller → battery54.7 A60 A70 Awithin
battery → inverter96.9 A100 A110 Awithin

Battery arrangement

ArrangementChemistryUnitsUnit capacityBank capacityNominal energyNominal voltage
4S1PLiFePO₄4100 Ah100 Ah5,120 Wh48 V

Static routed parts list

Parts are computed from this passing configuration. A route appears only when the verified catalogue record proves every displayed numeric rating; all uncertain matches stay local for verification. Routed links may earn Off Grid Authority a commission at no extra cost to you.

6 × 350 W solar panelVoc 45 V, Vmp 37 V, Isc 10 AVerify locally — no proven catalogue match
1 × MPPT charge controllerat least 55 A output and 169 V PV inputVerify locally — no proven catalogue match
4 × 100 Ah LiFePO₄ battery4S1P bank, 5120 Wh nominalVerify locally — no proven catalogue match
1 × 3350 W inverter6700 W surge, 48 V DC inputVerify locally — no proven catalogue match
70 ft × 8 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 8 AWGVerify locally — no proven catalogue match
1 × 35 A breaker / fuseDC-rated, 111 V system — must not exceed the wire's 40 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
25 ft × 4 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 4 AWGVerify locally — no proven catalogue match
1 × 60 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 70 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
20 ft × 1 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 1 AWGVerify locally — no proven catalogue match
1 × 100 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 110 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match

Pre-install review steps

  1. Confirm the array and controller window: Verify that the 3S2P string plan produces 135 V open circuit and that the equipment is rated above the 168.8 V cold-design value.
  2. Lay out the protected DC runs: Measure the one-way paths before ordering cable, then compare them with the computed 32 ft, 8 ft and 6 ft runs shown here.
  3. Build complete battery strings: Arrange all 4 battery units as 4S1P; do not leave a partial series string in a 48 V bank.
  4. Commission against equipment instructions: Check polarity, terminal torque, DC interrupt ratings, conductor temperature ratings, ambient correction and local inspection requirements before energizing the 3,350 W inverter.

Customize or compare

Customize this diagram →

Open the parent build guide for the surrounding design context, safety notes and installation discussion.