Engine-checked · within

3kW 48V Well-Pump Solar Wiring Diagram Complete (4S2P)

Computed 3kW 48V well pump solar diagram: 4S2P array, wire gauges, OCPD, battery arrangement, routed parts and printable files.

3kW 48V Well-Pump Solar Wiring Diagram Complete (4S2P) showing 4S2P panels, MPPT controller, 4S2P battery bank, wire gauges and OCPD ratings
Computed from the values printed in the schedules below; not a permit set.
View the scalable diagram inline3kW 48V Well-Pump Solar Wiring Diagram Complete (4S2P)Computed 4S2P schematic for a 3 kW 48 V well pump system, including wire and OCPD labels.FIG. OGA-LIBRARY-1193kW 48V Well-Pump Solar Wiring Diagram Complete (4S2P)COMPUTED FROM OGA CALC-CORE · NOT A PERMIT SET8 AWG · 35 A OCPD · 1.06% drop3 AWG · 80 A OCPD · 0.64% drop1 AWG · 110 A OCPD · 0.11% drop8 × 375 W panels4S2P · 190 Voc / 19.8 IscCombiner2 stringsDC disconnect35 A DC ratedMPPT controller79 A min · 300 V max80 A OCPDController output8 × 120 Ah AGM4S2P · 11520 Wh bank110 A OCPDInverter feed3700 W inverter7400 W surge · 85.6 A DCShunt85.6 A monitored returnGround busEquipment groundingarray → controller8 AWG · 35 A OCPD · 1.06% drop35 ft one way · Coppercontroller → battery3 AWG · 80 A OCPD · 0.64% drop10 ft one way · Copperbattery → inverter1 AWG · 110 A OCPD · 0.11% drop2 ft one way · CopperPOSITIVENEGATIVEEQUIPMENT GROUNDFAILING SEGMENTNEC 2023 Table 310.16 (60 C column) - conductor ampacityNEC Chapter 9, Table 8 - conductor DC resistanceNEC 240.6(A) - standard overcurrent-device ratingsNEC 210.19 / 215.2 - 125% continuous-load conductor sizingNEC 690.7 - maximum PV source-circuit voltageNEC 690.8 - PV source-circuit current sizingVerify equipment terminals, listings, ambient/bundling derates and local code before installation.

What this computed plan shows

This well pump drawing starts with 8 × 375 W modules and ends with a protected 3,700 W inverter feed. Between those points, the 3kW 48V Well-Pump Solar Wiring Diagram Complete (4S2P) preserves the exact 4S2P topology and 48 V bank selected in the catalogue. The drawing and schedules are regenerated from one shared system object to prevent labels from drifting apart.

A MPPT device is shown because the array and bank operate at different useful voltage points. The engine calculates 78.1 A of required controller output and tests 237.5 V against a 300 V input rating. These limits should be matched to a manufacturer datasheet, including its temperature assumptions.

The array-to-controller route is 35 ft one way and carries 30.9 design amps. It resolves to 8 AWG copper, a 35 A OCPD and 1.06% calculated drop. Downstream, the 10 ft controller lead uses 3 AWG copper behind 80 A protection, holding its computed drop to 0.64%.

The battery table translates 8 individual 120 Ah units into a 4S2P bank. In this 48 V design, the result is 240 Ah and 11,520 Wh of nominal storage. Usable energy will be lower and depends on chemistry limits, temperature, battery management and the connected load profile.

At the final DC segment, the current rises to 85.6 A for a 3,700 W inverter. The page assigns 1 AWG copper to the 2 ft route, with 110 A OCPD and 0.11% calculated drop. Termination ratings and the inverter maker’s fuse instructions remain controlling.

The generated SVG, PNG and tables intentionally repeat the same computed labels so discrepancies are visible during review. If a purchased controller, battery or inverter differs from the values above, regenerate the design from the linked machine before wiring. This well pump example is not a permit set and does not replace equipment instructions or a qualified local professional.

For later comparison, keep the 3 kW array, 4S2P bank and the 35/10/2 ft one-way routes together when requesting equipment quotes or an inspection review.

Wire, protection and battery schedules

Wire schedule

SegmentDesign currentOne-way runComputed conductorVoltage dropSizing basis
array → controller30.9 A35 ft8 AWG copper1.06%156% of array Isc (NEC 690.8)
controller → battery62.5 A10 ft3 AWG copper0.64%controller output at 125% continuous-load ampacity
battery → inverter85.6 A2 ft1 AWG copper0.11%inverter continuous DC input at 90% efficiency and 125% ampacity

Overcurrent protection

Protected segmentRequired ampacityOCPDConductor ampacityVerdict
array → controller30.9 A35 A40 Awithin
controller → battery78.1 A80 A85 Awithin
battery → inverter107.1 A110 A110 Awithin

Battery arrangement

ArrangementChemistryUnitsUnit capacityBank capacityNominal energyNominal voltage
4S2PAGM8120 Ah240 Ah11,520 Wh48 V

Static routed parts list

Parts are computed from this passing configuration. A route appears only when the verified catalogue record proves every displayed numeric rating; all uncertain matches stay local for verification. Routed links may earn Off Grid Authority a commission at no extra cost to you.

8 × 375 W solar panelVoc 47.5 V, Vmp 39.5 V, Isc 9.9 AVerify locally — no proven catalogue match
1 × MPPT charge controllerat least 79 A output and 238 V PV inputVerify locally — no proven catalogue match
8 × 120 Ah AGM battery4S2P bank, 11520 Wh nominalVerify locally — no proven catalogue match
1 × 3700 W inverter7400 W surge, 48 V DC inputVerify locally — no proven catalogue match
80 ft × 8 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 8 AWGVerify locally — no proven catalogue match
1 × 35 A breaker / fuseDC-rated, 158 V system — must not exceed the wire's 40 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
30 ft × 3 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 3 AWGVerify locally — no proven catalogue match
1 × 80 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 85 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match
10 ft × 1 AWG Copper cableTHHN/THWN-2 copper (or UL-listed battery cable), 75°C+Verify locally — no proven catalogue match
2 × Ring/lug terminalstinned, sized for 1 AWGVerify locally — no proven catalogue match
1 × 110 A breaker / fuseDC-rated, 48 V system — must not exceed the wire's 110 A ratingVerify locally — no proven catalogue match
1 pr × Heat-shrink + ferrulesadhesive-lined, color-codedVerify locally — no proven catalogue match

Pre-install review steps

  1. Confirm the array and controller window: Verify that the 4S2P string plan produces 190 V open circuit and that the equipment is rated above the 237.5 V cold-design value.
  2. Lay out the protected DC runs: Measure the one-way paths before ordering cable, then compare them with the computed 35 ft, 10 ft and 2 ft runs shown here.
  3. Build complete battery strings: Arrange all 8 battery units as 4S2P; do not leave a partial series string in a 48 V bank.
  4. Commission against equipment instructions: Check polarity, terminal torque, DC interrupt ratings, conductor temperature ratings, ambient correction and local inspection requirements before energizing the 3,700 W inverter.

Customize or compare

Customize this diagram →

Open the parent build guide for the surrounding design context, safety notes and installation discussion.